7SURTA 1500XL/1500XLJ/2200XL Series 100/120 Vac Tower/Rack-Mount 2U
Configuration
UPS Settings
Configure the settings using PowerChute software, a network management card or terminal mode.
Function Factory Default Options Description
Automatic
Self-Test
On startup and every
14 days (336 hours)
there after
On startup and every
7 days (168 hours)
there after
On startup and every 14
days
(336 hours) there after
On startup only
No self-test
Set the interval at which the UPS will
execute self-tests.
UPS ID UPS_IDEN Use a maximum of eight
alphanumeric characters to
define a name for the UPS.
Uniquely identify the UPS, i.e. server name
or location for network management
purposes.
Date of Last
Battery
Replacement
Manufacture
Date
mm/dd/yy Reset this date when the battery module is
replaced.
Minimum Capacity
Before Return from
Shutdown
0 percent 0%
•15%
•30%
•60%
•75%
•90%
Specify the percentage to which batteries
will be charged following a low-battery
shutdown, before sending power to
connected equipment.
Alarm Delay
Control
Enable Enable
•Mute
Disable Specify the delay between an event and the
alarm to avoid alarms for insignificant
events.
Shutdown Delay 90 seconds 0 sec
•90 sec
•180 sec
•270 sec
•360 sec
•450 sec
•540 sec
•630 sec
Specify the delay between the UPS
shutdown command and the actual
shutdown.
Duration of
Low Battery
Warning
2 minutes 2 min
•5 min
•8 min
•11 min
•14 min
•17 min
•20 min
•23 min
Specify the number of minutes before
system shutdown, after the low battery
warning.
Synchronized
Turn-on Delay
0 seconds 0 sec
•60 sec
•120 sec
•180 sec
•240 sec
•300 sec
•360 sec
•420 sec
Specify the delay between the return of
utility power and the UPS turns on. Set the
interval to avoid a branch circuit overload
condition.
High Bypass Points 100 Vac models
110 Vac
•107 Vac
•110 Vac
•113 Vac
•116 Vac
•119 Vac
•122 Vac
•125 Vac
•128 Vac
Maximum voltage that the UPS will pass to
connected equipment during internal bypass
operation.
120 Vac models
133 Vac
•127 Vac
•130 Vac
•133 Vac
•136 Vac
•139 Vac
•142 Vac
•145 Vac
•148 Vac